acar S8 IEC is a modern surge protective device, featuring 8 socket outlets with earthing pin and protective shutters as well as a power plug in the IEC 60320 C14 standard. Such equipment of the device predisposes it for professional use, and the automatic fuse used makes it a virtually maintenance-free device. Its high efficiency and reliability predispose the device to become the basic surge protector, which is necessary for every application.

Mounting brackets are optional and available from the distributor.

Colour

Power cord length

, ,

Przekrój żył

Type of plug

Number of socket outlets

Type of fuse

IEC Plug

Type of socket outlets

Mounting

,

SKU: N/A Category:

acar S8 IEC is a modern surge protective device, featuring 8 socket outlets with earthing pin and protective shutters as well as a power plug in the IEC 60320 C14 standard. Such equipment of the device predisposes it for professional use, and the automatic fuse used makes it a virtually maintenance-free device. Its high efficiency and reliability predispose the device to become the basic surge protector, which is necessary for every application.

Mounting brackets are optional and available from the distributor.

TECHNICAL DATA

Maximum load PMAX 2300W
Nominal voltage UN 230V
Nominal frequency 50Hz
Nominal load current ΣIN =10A MAX
Surge protection response time <25ns
Maximum voltage UC 250V 50Hz
Protection level UP ≤1,3kV
Nominal discharge current iN 2kA (L/N) – 8/20µs
Maximum discharge current iMAX 6,5kA (L/N) – 8/20µs
Fuses 1 automatic fuse, slow blow, 10A/250V
Anti-shock protection system earthing pins connected to the protective earthing conductor
Number of socket outlets 8 two-pole socket outlets with earthing pin, 10A/250V
Switch illuminated double pole mains switch
Housing made of self-extinguishing plastic
Dimensions 445x54x55mm
Weight 0,48kg