RS485 Protector

RS485 Protector

0,00

The AXON RS485 Protector is designed for surge protection of electronic appliances operating in industrial control systems based on RS485 transmission or variants thereof with the voltage not higher than 5V. The device incorporates protective elements that limit overvoltages between the transmission lines and the PE protective wire and simultaneously discharges the surge energy to the earth. The device also uses protective elements to limit the dangerous voltage that may occur between lines A and B. With this extensive protection the AXON RS485 Protector protects the connected equipment in a comprehensive way. The device features a metal, shielding housing. Three-way, detachable clamp terminals are used as the connection elements. Terminals A and B are used to connect transmission lines to be protected, while the third terminal can be used by the installer as a signal earth if required. The earthing wire terminated with a fork terminal is led out of the housing and connected directly to it. The device is asymmetric surge protector. The transmission line should be connected to the “Line” terminals, while the “Equip.” terminal is used to connect the protected appliance.

Purpose

Type of protected lines

Number of channels

Mounting type

SKU: W0048 Category:

The AXON RS485 Protector is designed for surge protection of electronic appliances operating in industrial control systems based on RS485 transmission or variants thereof with the voltage not higher than 5V. The device incorporates protective elements that limit overvoltages between the transmission lines and the PE protective wire and simultaneously discharges the surge energy to the earth. The device also uses protective elements to limit the dangerous voltage that may occur between lines A and B. With this extensive protection the AXON RS485 Protector protects the connected equipment in a comprehensive way. The device features a metal, shielding housing. Three-way, detachable clamp terminals are used as the connection elements. Terminals A and B are used to connect transmission lines to be protected, while the third terminal can be used by the installer as a signal earth if required. The earthing wire terminated with a fork terminal is led out of the housing and connected directly to it. The device is asymmetric surge protector. The transmission line should be connected to the “Line” terminals, while the “Equip.” terminal is used to connect the protected appliance.

TECHNICAL DATA

Nominal voltage UN 6V
Maximum voltage UC 10V
Nominal current IN 0.75A=
Level of protection UP line-line ≤16V – 1kV/µs, C3
Level of protection UP line-earthing ≤1000V – 1,2kV/50µs, C2
Nominal discharge current iN line-line 25A – 10/1000µs, C2
Nominal discharge current iN line-earthing 5kA – 8/20µs, C2
Serial impedance RS ≤2Ω
Bandwidth 0 – 1MHz
Line-line capacity 50pF
Line-earthing capacity 16pF
Standards PN-EN 61643-21
Type of sockets screw terminals max 1.5mm2, pluggable
Housing metal, powder coated
Dimensions 63x30x20mm
Weight 0,08 kg

The manufacturer reserves the right to change the technical parameters of the device, resulting from technological progress.
ATTENTION! The technical data define the maximum values of surges against which the device protects.