RS485 Protector DIN

RS485 Protector DIN

0,00

The AXON RS485 Protector DIN is designed for surge protection of electronic appliances operating in industrial control systems based on RS485 transmission or variants thereof with the voltage not higher than 5V. The device incorporates protective elements that limit overvoltages between the transmission lines and the PE protective wire and simultaneously discharges the surge energy to the earth. The device also uses protective elements to limit the dangerous voltage that may occur between lines A and B. With this extensive protection the AXON RS485 Protector DIN protects the connected equipment in a comprehensive way. The device‘s housing is designed for mounting in control and distribution cabinets equipped with the popular 35mm DIN rail. Terminals A and B are used to connect transmission lines to be protected, while the third terminal can be used by the installer as a signal earth if required. The earthing wire terminated with a fork terminal is led out of the housing and connected directly to it. The devices are asymmetric surge protectors. The transmission line should be connected to the “Line” terminals, while the “Equip.” terminal is used to connect the protected appliance.

Purpose

Type of protected lines

Number of channels

Mounting type

SKU: W0049 Category:

The AXON RS485 Protector DIN is designed for surge protection of electronic appliances operating in industrial control systems based on RS485 transmission or variants thereof with the voltage not higher than 5V. The device incorporates protective elements that limit overvoltages between the transmission lines and the PE protective wire and simultaneously discharges the surge energy to the earth. The device also uses protective elements to limit the dangerous voltage that may occur between lines A and B. With this extensive protection the AXON RS485 Protector DIN protects the connected equipment in a comprehensive way. The device‘s housing is designed for mounting in control and distribution cabinets equipped with the popular 35mm DIN rail. Terminals A and B are used to connect transmission lines to be protected, while the third terminal can be used by the installer as a signal earth if required. The earthing wire terminated with a fork terminal is led out of the housing and connected directly to it. The devices are asymmetric surge protectors. The transmission line should be connected to the “Line” terminals, while the “Equip.” terminal is used to connect the protected appliance.

TECHNICAL DATA

Nominal voltage UN6V
Maximum voltage UC10V
Nominal current IN0.75A=
Level of protection UP line-line≤16V – 1kV/µs, C3
Level of protection UP line-earthing≤1000V – 1,2kV/50µs, C2
Nominal discharge current iN line-line25A – 10/1000µs, C2
Nominal discharge current iN line-earthing5kA – 8/20µs, C2
Serial impedance RS≤2Ω
Bandwidth0 – 1MHz
Line-line capacity50pF
Line-earthing capacity16pF
StandardsPN-EN 61643-21
Type of socketsscrew terminals max 2.5mm2
Housingplastic, installation on 35mm rail, 1.5 modules wide
Dimensions90x58x22,5mm
Weight0,07 kg

The manufacturer reserves the right to change the technical parameters of the device, resulting from technological progress.
ATTENTION! The technical data define the maximum values of surges against which the device protects.